How to choose a series reactor

2020-10-16 15:06:26
Hits

Some time ago, Zhenhua editor told us a lot about Transformer and voltage Regulator, but Zhenhua Reactor is also professional. Today I take us to comment on how to select reactors


Reactor has reactance rate, which refers to the percentage of the additional capacity of series reactor to the additional capacity of capacitor or the percentage of inductive reactance XLN of series reactor to capacitance reactance xcn of capacitor. The selection of reactance rate also depends on the harmonic background


1. The background harmonic at the access point of capacitor equipment is 3 times


1) The third harmonic content is small, and 0.1% ~ 1% series reactor can be selected. However, it should be checked whether the third harmonic expansion exceeds or approaches the national standard limit after the capacitor equipment is put into operation, and there is a certain margin.


2) The third harmonic content is large, which has exceeded or approached the limit value of national standard. The mixed installation of 12% or 13% and 4.5% - 6% series reactors is selected.


2. The background harmonics at the access point of capacitor equipment are 3 times and 5 times


1) The third harmonic content is very small, and the fifth harmonic content is relatively large (including the limit value which has exceeded or is close to the national standard). Select 4.5% - 6% series reactor, and avoid using 0.1% - 1% series reactor.


2) The third harmonic content is slightly larger, and the fifth harmonic content is smaller. Select 0.1% ~ 1% series reactor, but check whether the third harmonic expansion exceeds or approaches the national standard limit after the capacitor equipment is put into operation, and there is a certain margin.


3) The third harmonic content is relatively large, which has exceeded or approached the limit value of national standard. The mixed installation of 12% or 12% and 4.5% - 6% series reactors is selected.


3. The background harmonic at the access point of capacitor equipment is 5 times or more


1) The fifth harmonic content is small, so 4.5% - 6% series reactor should be selected.


2) 5% series reactor should be selected because the 5th harmonic content is large.


4. When selecting 0.1% ~ 1% series reactors, it is necessary to prevent severe expansion or resonance of 5th and 7th harmonics; for selecting 4.5% ~ 6% series reactors, it is necessary to prevent severe expansion or resonance of 3rd harmonic

Xiaobian said so much today. If you want to know more, you are welcome to chat with Zhenhua Xiaobian

Label

Related News

SHANGHAI ZHENHUA TRANSFORMER MFG CO., LTD.

变压器设备,电抗器设备,稳压器设备 Tel:13816717555
变压器设备,电抗器设备,稳压器设备 Fixed:021-6989-3078
变压器设备,电抗器设备,稳压器设备 Email:sales@chzde.com
变压器设备,电抗器设备,稳压器设备

Address:No. 6, Pengpu Road, Jing'an District, Shanghai

Transformer Equipment, Reactor Equipment, Voltage Regulator Equipment

Scan And Follow Us